Segment 4: 1 - On if Fail To Communicate report enabled.
2 - On if Log Full report enabled.
3 - On if Autotest report enabled.
4 - On if Start/End programming report enabled.
5 - On if End Download report enabled.
6 - On if Sensor Low Battery report enabled.
7 - On if Sensor Missing report enabled.
8 - Reserved.
Segment 5: 1 = On enable Lost Clock service light.
2 = On enables Zone Doubling (Must have extra devices added to basic system to enable, refer to
page 7) (NX-200 Zone Doubling Kit required)
3 = On disables On-Board 4 zones.
4 = On will allow two trips on same cross-zone to activate an alarm.
5 = On will not allow zones that are force armed to report bypass.
6 = On enables Silent Exit option.
7 = Use internal crystal for clock.
8 = Disable Temporal Siren on Fire (NOTE: For UL installations, do NOT disable.) Refer to the
feature definitions beginning on page 3.
LOCATION 38 - SWINGER SHUTDOWN COUNT
Location 38 contains the number of trips on a zone before that zone is bypassed automatically. Refer to the feature
definitions beginning on page 3. NOTE: For UL installations, this feature shall be disabled.
LOCATION 39 - KEYPAD SOUNDER CONTROL (1 segment, feature selection data)
Segment 1: 1 & 2 - Reserved.
3 - On if keypad sounds upon AC Power Failure.
4 - On if keypad sounds when a Low Battery is detected.
5 - On if keypad sounds during Cross Zone trip time.
6 - On if keypad sounds for zone and box tampers.
7 - Reserved.
8 - On if keypad sounds for expander trouble (required for UL installations).
LOCATION 40 - SYSTEM TIMERS (10 segments, numerical data)
Location 40 contains the duration of various system timing functions. Example: If you desire the duration of the
Dynamic Battery Test to be 30 minutes, you should program [3]-[0]-[r] in segment 1 of this location. The [3]-[0]
is the number of minutes, and the [r] stores the data and moves to the next segment of this location.
Segment 1 Dynamic Battery Test duration in minutes 0-255 minutes ("0" = no test)
Segment 2 AC Fail report delay in minutes 0-255 minutes.
Segment 3 Power Up Delay in seconds 0-60 seconds ("0" = no power up delay).
Segment 4 Siren Time in minutes 1-255 minutes.
Segment 5 Reserved.
Segment 6 Cross Zone time in minutes 0-255 ("0" = no cross zoning).
Segment 7 Chime time in 50 mS (1/20th second) increments from 0-12 seconds ("0" = follows zone 255 latched).
Segment 8 Dial delay in seconds 0-255 seconds (0 no abort delay).
Segment 9 Fire Alarm Verification time in seconds 120-255 seconds ("0" = no fire alarm verification).
Segment 10 Listen-In time in seconds 0-255 (" 0" = no Listen-In time).
IMPORTANT NOTES
1. The "Listen-In" feature cannot be enabled for UL Listed systems. The "Dynamic Battery Test" feature cannot
exceed four (4) hours. The dial delay shall be set to A0".
2. For household systems, the Fire Alarm Verification feature is NOT approved for use in California. This feature
shall not be programmed into the control unit.